VENT-FREE PROPANE/LP GAS COMPACT FIREPLACE
CGCFTP
ON
POSITION
OFF
POSITION
Open
Closed
Equipment
Shutoff
Valve
Figure 28 - Checking Gas Joints Shown with Optional Mantel
Figure 27 - Equipment Shutoff Valve
Equipment
Shutoff
Valve
Propane/LP
Supply Tank
CHECKING GAS
CONNECTIONS
Pressure Testing Gas Supply
Piping System
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance
main gas valve (control valve) and equip-
ment shutoff valve from gas supply pip-
ing system. Pressures in excess of 1/2
psig will damage heater regulator.
2. Cap off open end of gas pipe where
equipment shutoff valve was connected.
3. Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.
4. Check all joints of gas supply piping
system. Apply a noncorrosive leak de-
tection fluid to gas joints. Bubbles
forming show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment
shutoff valve to gas supply. Check re-
connected fittings for leaks.
WARNING: Test all gas pip-
ing and connections for leaks
after installing or servicing. Cor-
rect all leaks at once.
WARNING: Never use an open
flame to check for a leak. Apply a
noncorrosive leak detection fluid
to all joints. Bubbles forming show
a leak. Correct all leaks at once.
CAUTION: Make sure external
regulator has been installed be-
tween propane/LP supply and fire-
place. See guidelines under
Con-
necting to Gas Supply
, page 14.
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-
ure 27).
2. Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.
3. Check all joints from propane/LP sup-
ply tank to equipment shutoff valve (see
Figure 28). Apply a noncorrosive leak
detection fluid to gas joints. Bubbles
forming show a leak.
4. Correct all leaks at once.
Pressure Testing Fireplace Gas
Connections
1. Open equipment shutoff valve (see Fig-
ure 27).
2. Open propane/LP supply tank valve.
3. Make sure control knob of fireplace is
in the OFF position.
4. Check all joints from equipment shutoff
valve to thermostat gas valve (see Fig-
ure 28). Apply a noncorrosive leak de-
tection fluid to gas joints. Bubbles
forming show a leak.
5. Correct all leaks at once.
6. Light fireplace (see Operating Fire-
place, pages 17 and 18). Check all other
internal joints for leaks.
7. Turn off fireplace (see To Turn Off Gas
to Appliance, page 18).
8. Replace front panel.